25 mm² to AWG

25 mm² equals
4 AWG
closest AWG: 4 AWG · precise AWG cross-section: 21.15 mm²

4 AWG is where DC wiring stops being light branch circuits and starts being serious power transmission. It is the default for battery bank interconnects, feeds to medium inverters (1000–1500 W class at 12V), and the main distribution between battery and fuse panel. At this gauge, friction-fit terminals stop being acceptable — every 4 AWG termination needs a hexagonal crimp die, heat-shrink, and ideally a torque-checked stud connection.

All values on this page assume copper conductors at 20°C ambient. Aluminum has ~60% higher resistance for the same cross-section and is generally not recommended for low-voltage DC.

Cross-section
25 mm²
21.15 mm² precise IEC
Ampacity
85 A
copper, chassis, 20°C
Max Fuse
85 A
ANL
Resistance
0.71 mΩ/m
copper at 20°C

Calculate for your specific cable run

The tables below assume 4 AWG (25 mm²) copper. Use the calculator to confirm this gauge is correct for your exact load and length, or get a different gauge recommendation if needed.

V
0V48V
A
0A200A

= 60W

m
0m30m

= 16.4 ft (one way, round-trip calculated automatically)

Advanced Settings

Result

Wire size meets all requirements.
Recommended Wire
2.5 mm²
13 AWG
Voltage Drop
0.36V
3.0% of 12V
Power Loss
1.8W
Resistance
71.4

Fuse Size

Fuse Size
7.5A
Fuse Type
Blade (ATC/ATO)
Standard automotive blade fuse. Place inline near the power source.
Always place the fuse as close to the power source (battery) as possible. The fuse protects the wire, not the load.

Need a complete wiring diagram?

VoltPlan designs full electrical systems for campers, boats, and off-grid setups with automatic wire sizing, fuse placement, and solar configurations.

Design Your System

Wire sizing on the go?

Cable by VoltPlan is our iOS app for quick DC wire sizing, fuse recommendations, and AWG/mm² conversions -- right in the hardware store.

Download Cable for iOS
Wire Gauge
2.5mm²
Fuse Size
7.5A
Voltage Drop
3.0%
Power Loss
1.8W

4 AWG Voltage Drop at 12V DC

Round-trip voltage drop for 4 AWG (25 mm²) copper wire at 20°C ambient. Cells highlighted in yellow exceed the 3% target; red cells exceed 5% and are not recommended.

Current1 m / 3 ft3 m / 10 ft5 m / 16 ft10 m / 33 ft20 m / 66 ft
20 A0.029 V (0.24%)0.086 V (0.71%)0.14 V (1.19%)0.29 V (2.38%)0.57 V (4.76%)
40 A0.057 V (0.48%)0.17 V (1.43%)0.29 V (2.38%)0.57 V (4.76%)1.14 V (9.52%)
60 A0.086 V (0.71%)0.26 V (2.14%)0.43 V (3.57%)0.86 V (7.14%)1.71 V (14.28%)
80 A0.11 V (0.95%)0.34 V (2.86%)0.57 V (4.76%)1.14 V (9.52%)2.28 V (19.04%)
100 A0.14 V (1.19%)0.43 V (3.57%)0.71 V (5.95%)1.43 V (11.90%)2.86 V (23.80%)

4 AWG Voltage Drop at 24V DC

Round-trip voltage drop for 4 AWG (25 mm²) copper wire at 20°C ambient. Cells highlighted in yellow exceed the 3% target; red cells exceed 5% and are not recommended.

Current1 m / 3 ft3 m / 10 ft5 m / 16 ft10 m / 33 ft20 m / 66 ft
20 A0.029 V (0.12%)0.086 V (0.36%)0.14 V (0.60%)0.29 V (1.19%)0.57 V (2.38%)
40 A0.057 V (0.24%)0.17 V (0.71%)0.29 V (1.19%)0.57 V (2.38%)1.14 V (4.76%)
60 A0.086 V (0.36%)0.26 V (1.07%)0.43 V (1.79%)0.86 V (3.57%)1.71 V (7.14%)
80 A0.11 V (0.48%)0.34 V (1.43%)0.57 V (2.38%)1.14 V (4.76%)2.28 V (9.52%)
100 A0.14 V (0.60%)0.43 V (1.79%)0.71 V (2.97%)1.43 V (5.95%)2.86 V (11.90%)

What is 4 AWG (25 mm²) used for?

Camper / RV applications

  • Battery bank interconnects (2–4 batteries in parallel)
  • Inverter feeds up to 1500 W at 12V (~125 A)
  • Main battery-to-fuse-panel distribution cable
  • Large MPPT to battery on 60–80 A controllers
  • B2B (DC-DC) chargers above 40 A

Boat / marine applications

  • House-bank battery interconnects
  • Windlass feed on medium-size boats
  • Inverter feeds for refrigeration and AC outlets
  • Alternator-to-battery on systems with high-output alternators
  • Bow thruster on smaller boats (under 4 kW)

Off-grid / solar applications

  • Battery bank interconnects (lithium parallel banks)
  • 1500–2000 W inverter feeds at 12V or 3000 W at 24V
  • Main battery cabinet wiring
  • Class T or ANL fuse to bus bar feeds

When to step up

  • Inverter loads above 1500 W at 12V — needs 2 AWG or 1/0
  • Battery banks above 400 Ah parallel — heavier interconnect cables
  • Continuous current above 70 A — close to ampacity
  • Cable runs longer than 4 m at 12V with currents above 60 A

Fuse size for 4 AWG (25 mm²)

The fuse must protect the wire, not the load. For 4 AWG copper (25 mm²) the maximum fuse rating is 85 A. Below this ceiling, size the fuse at 125% of your continuous load current and round up to the next standard fuse size.

Continuous Load125% CalculationRecommended FuseFuse Type
10 A12.5 A15 ABlade (ATC)
15 A18.75 A20 ABlade (ATC)
20 A25 A25 ABlade (ATC)
55 A68.75 A70 AANL
80 A100 A100 AANL
Placement rule: place the fuse within 18 cm (7 inches) of the battery positive terminal. The unprotected wire between battery and fuse should be as short as possible — if it shorts to chassis, there is nothing to prevent a fire.

Related conversions

Frequently Asked Questions

What is 25 mm² in AWG?

25 mm² is the metric pairing for 4 AWG in international cable standards. The precise AWG value of 25 mm² is between 3 AWG (26.7 mm²) and 4 AWG (21.15 mm²) — closer to 3 AWG. In practice, 25 mm² and 4 AWG are matched in cable spec tables and used interchangeably.

How many amps can 25 mm² wire handle?

25 mm² copper cable is rated for 85 A continuous at 20°C in chassis wiring — the same ampacity as 4 AWG. For high-temperature engine compartments or bundled cable runs, derate by 10–20%.

Is 25 mm² enough for an inverter?

For inverters up to 1000 W at 12V (~85 A continuous), 25 mm² works at the limit. For 1500 W or larger inverters at 12V, step up to 35 mm² (2 AWG) or 50 mm² (1 AWG). At 24V, 25 mm² handles inverters up to 2000 W comfortably.

What size fuse for 25 mm² cable?

Maximum fuse for 25 mm² is 85 A. Below that ceiling, size at 125% of continuous load: 60 A load → 80 A fuse, 70 A load → 100 A (or step up cable size). Use ANL or Class T fuses at this current level — blade fuses are not appropriate.