2.5 mm² to AWG

2.5 mm² equals
13 AWG
closest AWG: 13 AWG · precise AWG cross-section: 2.62 mm²

2.5 mm² is the single most stocked cable size in European auto-electrical and marine shops — the default for every branch circuit that outgrows 1.5 mm². Its AWG twin is the oddball: 13 AWG (2.62 mm²) sits between the common even sizes 14 and 12 AWG and is rarely sold in North America. That is why 2.5 mm² datasheets list "13 AWG equivalent" while US shopping lists round to 12 AWG for the same job. At 20 A ampacity, 2.5 mm² covers combined lighting trunks, fridge branches, and heavy accessory circuits.

All values on this page assume copper conductors at 20°C ambient. Aluminum has ~60% higher resistance for the same cross-section and is generally not recommended for low-voltage DC.

Cross-section
2.5 mm²
2.62 mm² precise IEC
Ampacity
20 A
copper, chassis, 20°C
Max Fuse
20 A
Blade (ATC)
Resistance
7.14 mΩ/m
copper at 20°C

Calculate for your specific cable run

The tables below assume 13 AWG (2.5 mm²) copper. Use the calculator to confirm this gauge is correct for your exact load and length, or get a different gauge recommendation if needed.

V
0V48V
A
0A200A

= 60W

m
0m30m

= 16.4 ft (one way, round-trip calculated automatically)

Advanced Settings

Result

Wire size meets all requirements.
Recommended Wire
2.5 mm²
13 AWG
Voltage Drop
0.36V
3.0% of 12V
Power Loss
1.8W
Resistance
71.4

Fuse Size

Fuse Size
7.5A
Fuse Type
Blade (ATC/ATO)
Standard automotive blade fuse. Place inline near the power source.
Always place the fuse as close to the power source (battery) as possible. The fuse protects the wire, not the load.

Need a complete wiring diagram?

VoltPlan designs full electrical systems for campers, boats, and off-grid setups with automatic wire sizing, fuse placement, and solar configurations.

Design Your System

Wire sizing on the go?

Cable by VoltPlan is our iOS app for quick DC wire sizing, fuse recommendations, and AWG/mm² conversions -- right in the hardware store.

Download Cable for iOS
Wire Gauge
2.5mm²
Fuse Size
7.5A
Voltage Drop
3.0%
Power Loss
1.8W

13 AWG Voltage Drop at 12V DC

Round-trip voltage drop for 13 AWG (2.5 mm²) copper wire at 20°C ambient. Cells highlighted in yellow exceed the 3% target; red cells exceed 5% and are not recommended.

Current1 m / 3 ft2 m / 7 ft3 m / 10 ft5 m / 16 ft7 m / 23 ft
3 A0.043 V (0.36%)0.086 V (0.71%)0.13 V (1.07%)0.21 V (1.79%)0.30 V (2.50%)
5 A0.071 V (0.59%)0.14 V (1.19%)0.21 V (1.79%)0.36 V (2.97%)0.50 V (4.17%)
10 A0.14 V (1.19%)0.29 V (2.38%)0.43 V (3.57%)0.71 V (5.95%)1.00 V (8.33%)
15 A0.21 V (1.79%)0.43 V (3.57%)0.64 V (5.35%)1.07 V (8.92%)1.50 V (12.49%)
20 A0.29 V (2.38%)0.57 V (4.76%)0.86 V (7.14%)1.43 V (11.90%)2.00 V (16.66%)

13 AWG Voltage Drop at 24V DC

Round-trip voltage drop for 13 AWG (2.5 mm²) copper wire at 20°C ambient. Cells highlighted in yellow exceed the 3% target; red cells exceed 5% and are not recommended.

Current1 m / 3 ft2 m / 7 ft3 m / 10 ft5 m / 16 ft7 m / 23 ft
3 A0.043 V (0.18%)0.086 V (0.36%)0.13 V (0.54%)0.21 V (0.89%)0.30 V (1.25%)
5 A0.071 V (0.30%)0.14 V (0.59%)0.21 V (0.89%)0.36 V (1.49%)0.50 V (2.08%)
10 A0.14 V (0.59%)0.29 V (1.19%)0.43 V (1.79%)0.71 V (2.97%)1.00 V (4.17%)
15 A0.21 V (0.89%)0.43 V (1.79%)0.64 V (2.68%)1.07 V (4.46%)1.50 V (6.25%)
20 A0.29 V (1.19%)0.57 V (2.38%)0.86 V (3.57%)1.43 V (5.95%)2.00 V (8.33%)

What is 13 AWG (2.5 mm²) used for?

Camper / RV applications

  • Combined lighting trunk lines feeding several zones (8–15 A)
  • Compressor fridge branches up to 10 A continuous
  • 12V distribution to USB-C PD outlets (100 W chargers pull ~9 A)
  • Water pumps up to 10 A continuous with inrush headroom
  • Diesel heater feeds (Autoterm, Webasto — 10–15 A glow-plug phase)

Boat / marine applications

  • Cabin lighting trunks and spreader lights
  • Freshwater and washdown pumps up to 10 A
  • Instrument buses combining plotter, VHF, and AIS
  • Fridge branch circuits on daysailers
  • Windlass control (not feed) circuits

Off-grid / solar applications

  • Lighting and outlet branches in tiny homes and cabins
  • PV string wiring for single panels up to 20 A
  • Shed sub-feeds for lighting plus router/monitoring loads
  • Fan and ventilation circuits

When to step up

  • Continuous current above 16 A — within 20% of ampacity
  • Cable runs longer than 5 m at 12V with currents above 10 A
  • Motor loads with inrush above 25 A (pumps, blowers) — use 4 mm²
  • Any feed you might later extend: 4 mm² costs cents more per metre

Fuse size for 13 AWG (2.5 mm²)

The fuse must protect the wire, not the load. For 13 AWG copper (2.5 mm²) the maximum fuse rating is 20 A. Below this ceiling, size the fuse at 125% of your continuous load current and round up to the next standard fuse size.

Continuous Load125% CalculationRecommended FuseFuse Type
2 A2.5 A5 ABlade (ATC)
5 A6.25 A7.5 ABlade (ATC)
8 A10 A10 ABlade (ATC)
10 A12.5 A15 ABlade (ATC)
17 A21.25 A20 ABlade (ATC)
Placement rule: place the fuse within 18 cm (7 inches) of the battery positive terminal. The unprotected wire between battery and fuse should be as short as possible — if it shorts to chassis, there is nothing to prevent a fire.

Related conversions

Frequently Asked Questions

What is 2.5 mm² in AWG?

2.5 mm² converts to 13 AWG (2.62 mm² precise) — closer to 13 AWG than to 14 AWG (2.08 mm²). Because 13 AWG is rarely sold in North America, the practical substitutes are 12 AWG (3.31 mm², safe in both directions) or 14 AWG where the load stays under 15 A.

How many amps can 2.5 mm² wire handle?

2.5 mm² copper cable is rated for 20 A continuous at 20°C in chassis wiring. It is the standard European size for branch circuits that outgrow 1.5 mm²: combined lighting trunks, fridge branches, water pumps, and diesel heaters.

Is 2.5 mm² enough for a 12V fridge?

Yes for typical 12V compressor fridges (Dometic CRX, Vitrifrigo) drawing 4–7 A continuous with ~15 A inrush. Keep the run under 6 m at 12V for under 3% voltage drop. For chest fridges above 10 A continuous or runs beyond 8 m, use 4 mm².

What size fuse for 2.5 mm² cable?

Maximum 20 A. Size the fuse at 125% of the continuous load and round up: a 7 A fridge takes a 10 A fuse, a 12 A heater feed takes a 15 A fuse. Use standard ATC/ATO blade fuses at this current level.

Should I use 2.5 mm² or 4 mm² for my camper build?

Use 2.5 mm² for branch circuits up to 16 A continuous and runs under 5 m. Use 4 mm² for anything with motor inrush (pumps, blowers), runs beyond 5 m, or circuits you may extend later. Many builders standardize on 2.5 mm² for branches and 4–6 mm² for feeds — two spools cover the whole interior.